Recent Articles
How to simulate proving using a FlowX flow computer
How to simulate proving with the Flow-X flow computer This How to instruction will provide an example of how to program the FlowX to simulate proving a meter. Most newer flow computers require live pulses and detector inputs to prove a meter. Wiring ...
IO Calibration
Calibration Calibration can be done on two levels 1. I/O calibration Calibration of analog inputs, PT-100 inputs and analog outputs 2. Calibration of process inputs Loop calibration of any process input (temperature, pressure, density, viscosity, ...
How to request and install a Flow-Xpress License
HOW TO INSTALL FLOW XPRESS SOFTWARE & LICENSE HOW TO INSTALL FLOW XPRESS SOFTWARE & LICENSE To download the Flow Xpress software go to the download site at https://www.crt-services.com/support/. Once the software is downloaded, please complete the ...
Flow-X Analog output calibration
The procedure to calibrate an analog output is based on a 4-20 mA meter. 1. Connect the mA meter in series with the load. 2. Go to the analog output calibration display. Display → Diagnostics, IO, <Module x>, Calibration, Analog outputs With x the ...
How to print a snapshot report on startup in Flow-X
PRINT A SNAPSHOT REPORT ON STARTUP IN FLOW-X This document describes how to generate a snapshot repot whenever the Flow-X flow computer starts up for any reason. Define a new Calculation group Define a new tag to latch the latest startup time Give ...